Steel Pipes – Thermal Expansion Loops

Steel Pipes – Thermal Expansion Loops

Calculating and sizing steel pipe thermal expansion loops.

The expansion loop is a common way to absorb temperature expansion and contraction in steel pipes. Expansion loops can be fabricated from standard pipes and elbows.

Steel pipe temperature U-bends expansion loops

Steel Pipes – Thermal Expansion Loops
Nominal Pipe Size
(mm)
Approximate Expansion Capacity (mm) 
Width of Expansion Loop – w – (m) 
0.5 1.0 1.5 2.0 2.5
25 35 130
32 25 100 210
40 20 70 150
50 65 125 200
65 50 100 150 220
80 40 75 125 190
100 35 65 115 150

Steel pipes - temperature expansion loops diagram

U-Bends Expansion Compensator Calculator

Metric Units

This calculator can be used to calculate required width and height of an U-bends expansions compensator.

Temperature expansion to be absorbed by the U-bends compensator (mm): 64.8

“Width” of loop (w) (m): 0.854

“Offset” of loop (2w) (m): 1.71

“Length” of loop (2 * 2w + w) (m): 4.27

Imperial Units

Temperature expansion to be absorbed by the U-bends compensator (in): 2.56

“Width” of loop (w) (in): 33.1

“Offset” of loop (2w) (in): 66.1

“Length” of loop (2 * 2w + w) (in): 165

The U-loops calculation is based on equation

w = 0.015 (dl D)1/2       (1)

where

w = width of loop (m)

dl = α dt S = temperature expansion (m)

α = temperature expansion coefficient (m/m oC)

dt = temperature change (oC)

S = length of expanding pipe (m)

D = diameter of pipe (m)

The offset of the loop is 2 w. The length of the loop is 5 w.

Z-Bends Expansion Compensator Calculator

z-bends expansion pipe line compensator

Metric Units

This calculator can be used to calculate required offset in a Z-bends expansions compensator.

Temperature expansion to be absorbed by the Z-bends compensator (mm): 64.8

“Offset” loop (w) (m): 3.59

Imperial Units

Temperature expansion to be absorbed by the Z-bends compensator (in): 2.56

“Offset” loop (w) (in): 139

L-Bends Expansion Compensator Calculator

l-bends expansion pipe line compensator

Metric Units

This calculator can be used to calculate required offset in a Z-bends expansions compensator.

Temperature expansion to be absorbed by the L-bends compensator (mm): 64.8

“Offset” loop (w) (m): 4.25

Imperial Units

This calculator can be used to calculate required offset in a Z-bends expansions compensator.

Temperature expansion to be absorbed by the L-bends compensator (in): 2.56

“Offset” loop (w) (in): 165

The L-loop calculation is based on equation

L = 0.063 (dl D)1/2       (2)

where

L = length of loop (m)

 

Để lại một bình luận